Important Formula : Corona Loss

( 1 ) Critical disruptive voltage

VC = m0go δ r Loge ( d / r )

Where VC = Phase to neutral voltage

              r = Radius of conductor

             d = Diameter of conductor

            g0 = Breakdown ( Dielectric ) strength of air at 76                     cm of mercury at 25 degree centigrade

                = 30 kV / cm ( Max )

                = 21.2 kV / cm ( RMS )

          m0 = Irregular factor

               = 1 for polished conductor

               = 0.98 to 0.92 for dirty conductor

              = 0.87 to 0.8 for stranded conductor

( 2 ) Air density factor

Air density factor δ = 3.92b / 273 + t

Where b = atmospheric pressure of b cm

            t = Temperature in centigrade

Line voltage = 3 × VC

( 3 ) Visual Critical voltage

VV = m0go δr { 1 + 0.3 / √ δr } Loge ( d / r )

Where

   m0 = Irregular factor

   g0 = Breakdown ( Dielectric ) strength of air

     r = Radius of conductor

     d = Diameter of conductor

     δ = Air density factor

( 4 ) Power loss due to corona

P = 242.2 ( f + 25 / δ ) √ r / d ( V – VC )2 × 10 – 5 kW / km / Phase

 Where

        f = Supply frequency

      V = Phase to neutral voltage ( RMS )

   VC = Critical disruptive voltage ( RMS ) per phase

      δ = Air density factor


Power loss due to corona α ( V – VC )2